    North Tower Rm 74 Retail Storage Sewage Pumps

    Found sewage pumps tripped on overloads.  Reset and pumped water down.  Pumps tripped again.  Had Electricians check out.  Currently trying to find pump info for amperage.  Also pipe has hole inside the pit.  Referred to John E Green for repairs.

  • Study Material

    Energy Center Shift Duties 1900hrs-0700hrs Cori

    Plant rounds and readings in the Energy Center.

    Warmed #3 Boiler, Blew down #1 Boiler and checked LWCO.

    Tested boiler water and cooling towers water.

    Med gas Manifold readings.

    Metasys Checks and Cold and/or warm calls.

    Helped Bill change filters in Mer 18 & 19.

    worked on P.M.’s.

    Boiler #1  sulfite low Added sulfite to boiler #1.

  • Study Material

    Power Plant 0700-1900 Dwight

    Warmed and blewdown boilers checked L.W.C.O. on #1 boiler

    Installed new flame scanner and amplifier, flame signal is 5.0 v

    pm #3 boiler ran on oil

    Rounds and readings

  • Study Material

    Energy Center Shift Duties 1900hrs-0700hrs Cori

    Plant rounds and readings in the Energy Center. Warmed #3 Boiler, Blew down  #1 Boiler and checked LWCO. Tested boiler water and cooling towers water.  Med gas Manifold readings. Metasys Checks and Cold and/or warm calls.

    Added 2.5 gal of halochlor to Yard Tower.

    Changed Thermostat in room 462.

    worked on P.M.’s.

    Metasys Alarm for SJMH Primary Bulk  Nitrogen Liquid Low.