• Metasys

    angio 2362C

    W.O for 2362 C being too cold.  Check area, 65 degrees.  Also noticed hallways were cold.  Check mer 13 t.u,. commanded off.    System Working as programmed. Lowly

  • Metasys

    COOLING TOWER LEVEL CONTROL

        The cooling tower for chiller 4 & the yard towers for chillers 1&2 have had the float valves removed and are under Metasys control (modulating ball valve near the make-up water meter). The tower level reading is the distance from…

  • Metasys

    O.R. Hybrid Room #1

    Found out through a bit of testing with a VANEOMETER; the door separating the control room section from the procedure area of Surgery’s O.R. Hybrid Room #1 needs to be closed to maintain proper room pressurization.  Thanks Cori for your efforts…

  • Metasys

    HYBRID ROOM #1 (in AIMS as HYBRIDOR1)

    Kyle Morrison from JCI will be here tomorrow morning at or around 6 AM to replace a faulty pressure sensor serving our HYBRID OPERATING ROOM.  (#2850)  As is now, the room has been overridden to maintain positive pressure conditions.  When finished,…