• Metasys

    ahu 50-30

    Found ahu 50-30 running at 46 degrees, cooling valve 18% open.  Shut down fan, power cycled jci panel.  Restart, currently holding setpoint Lowly

  • Study Material

    East Tower ahu 43-26

    5th floor static pressure in alarm on ahu 43-26.  Noticed static pressure set point on ahu was set at .5,  don’t know why this was changed.   Put back to 1.0″ alarm went back to normal. Lowly