    Power Plant 7am – 7pm

    Fix surgery chiller indicator(3) on metasys to show correct status. Med air and gas readings. Plant Rounds and readings. Warm up boiler 3. While warming up boiler 3 there was a quick and short alarm at the console and the pwc started flashing showing a lockout on boiler 3 and quickly cleared itself. I didn’t have to acknowledge or silence anything at the boiler, it stopped by itself. Reset pwc OK. Note: Boiler never shutdown for this alarm which it normally would do – must have happened too fast. Blow down boiler 1. Add salt to tanks. Finish graphic for Ann Arbor and WMAB Generators. Find it in the Generators…

  • Study Material

    Energy Center Shift Duties 1900hrs-0700hrs Cori

    Plant rounds and readings in the Energy Center. Warmed #3 Boiler, Blew down  #1 Boiler and checked LWCO. Tested boiler water and cooling towers water.  Med gas Manifold readings. Metasys Checks and Cold and/or warm calls. Changed Chiller Selection to 2, 3, 1, 4, so we can bring chemicals of yard tower up. Added 2 gal. of Halochlor to Yard tower. Electrical shut Down for surgery area, resetting equitment after it was completed. worked on P.M.’s.

  • Study Material

    East Tower domestic cold water hot

    Noticed while doing pm”s in MER 26 that domestic cold water was hot. Found By-pass for backflow preventer that serves water heaters was opened. Closed one side, water cooled down. Checked water flow in East tower, normal. Showed Cori what I closed just in case, don’t know why this was open.

  • Study Material

    Power Plant 9am – 7pm

    Blowdown boiler 1 and warm up boiler 3. Monitor metasys – adjust/dispatch  as needed. Plant rounds and readings. Utility readings. Check and record tower dip slide tests. Work on metasys graphics – North tower, generators. Work on engineering blog. R & L Carriers picked up empty eldon drums. General cleaning.

  • Study Material

    Energy Center Shift Duties 2300hrs-0700hrs Cori

    Plant rounds and readings in the Energy Center. Warmed #3 Boiler, Blew down  #1 Boiler and checked LWCO. Tested boiler water and cooling towers water.  Med gas Manifold readings. Metasys Checks and Cold and/or warm calls. Added 3 gal. of halochlor  and 1 qt. of defoamer to the Yard Tower. Added 1 gal. of Halochlor to the #3 Tower. Added sulfite to Boilers.